EARTHING
Earthing or earthing system is the total of all
means and measures by which part of an electrical circuit, accessible
conductive parts of electrical equipment (exposed conductive parts) or
conductive parts in the vicinity of an electrical installation (extraneous
conductive parts) are connected to earth.
Earth electrode is a metal conductor, or a
system of interconnected metal conductors, or other metal parts acting in the
same manner, embedded in the ground and electrically connected to it, or
embedded in the concrete, which is in contact with the earth over a large area
(e.g. foundation of a building).
Earthing conductor is a conductor which connects
a part of an electrical installation, exposed conductive parts or extraneous
conductive parts to an earth electrode or which interconnects earth electrodes.
The earthing conductor is laid above the soil or, if it is buried in the soil,
is insulated from it.
The
various standardized earthing system :
- when designing an electrical
instillation , one of the first things to determine is the type of earting
system
TYPE OF EARTHING SYSTEM
The three earting system given official status by
international standards (IEC60364)are also stipulated by alarge number of national
standards : infrance by the lv installation stanadard : NFC 15-100.
1-The TN system
Its principle
-
the transformer neutral is earthed
-
the electrical load frames are
connected to neutral
-this type of the system has three
possibilities
a)- TN – C
system
The same conductor
acts as a neutral and protective conductor (fig E-A)
B) TN – S system
C)- T N –C –
S system
An insulation fault on a phase becomes a short circuit and
the faulty part is disconnected by
a Short-Circuit Protection Device
(SCPD).
2- T
T system
-
the
transformer neutral is earthed
-
the
electrical load frames are also earthed
its
operation
The current of an insulation fault is limited by earth
connection impedance. Protection is provided by the Residual Current Devices
(RCD)
Its
principle
-the transformer neutral is not earthed,
but is theoretically unearthed. In actual fact, it is naturally earthed by the
stray capacities of the network cables
-the electrical load frames are earthed.
Its
operation:
- should an insulation fault occur, a low current develops
as a result of the network’s stray capacities (see fig. 3a ). The
contact voltage developed in the frame earth connection (no more than a few
volts) is not dangerous;
- if a second fault occurs on another phase before the
first fault has been eliminated
(see fig. 3b and 3c ), the frames of the
loads in question are brought to the potential developed by the fault current in the protective
conductor (PE) connecting them. The SCPDs (for the frames interconnected by the
PE) or the RCDs (for the frames with
separate earth connections) provide the necessary protection.
ليست هناك تعليقات: