عوامل اختيار القواطع الكهربية
(CBs)
تحدبد القيم المقننه التالية:
2- Initial symmetrical RMS current
3- The maximum possible dc. Component of short circuit current
4- The making capacity of the circuit breaker in kA
5- The RMS value of the symmetrical breaking current.
6- Asymmetrical breaking current
7- The interrupting capacity in MVA.
وسوف نعطى مثال لكيفية حسابات هذة القيم بفرض وجود مولد له البيانات
التالية
Three phase alternator
Power rated = 15 MVA
Voltage terminal = 6.6 KV
Subtransient reactance = 0.1 pu
Transient = 0.15 pu
Synchronous = 0.6 pu
وتم توصيل هذا المولد بقاطع دائرة من النوع الزيتى الصغير 5
Cycle – oil circuit breaker
وتكون خطوات الحساب كالتالى.
In power system, the circuit breakers provided should have ample capacity to make as well as break the circuit at the service voltage.
The breaking capacity ratings are expressed in terms of:
1- The symmetrical RMS current which can be broken all poles.
2- The max. Symmetrical RMS that can be interrupted on any one pole.
The former may be referred to in terms of MVA which is the product
1.73 * Line KV * symmetrical breaking current in KA.
The short circuit current against which the circuit breaker can remain closed during the first cycle of short circuit is called the ‘making current ’which may be taken as about
1.8X1.414= 2.546 Times the symmetrical RMS breaking current
Or 1.8 Times the peak value symmetrical breaking current
For 5-cycle circuit breaker the asymmetrical breaking current may be taken as about 1.4 times symmetrical breaking current.
In this problem, rated current of the alternator is
For 5-cycle circuit breaker the asymmetrical breaking current may be taken as about 1.4 times symmetrical breaking current.
In this problem, rated current of the alternator is
1 pu = 15000 / 1.73 * 6.6 = 1312 Amp.
1 pu = 6.6 KV
Subtransient reactance = 0.1 pu
Transient = 0.15 pu
Synchronous = 0.6 pu
1 – Steady short circuit = 1.0 / 0.6 = 1.66 pu
= 1.66 * 1312 = 2.18 KA
2 - Initial symmetrical RMS current = 1pu / Subtransient
reactance
= 1.0 / 0.1 = 10 pu
= 10 * 1312 =13.12 KA
3 – The maximum possible dc. Component of short circuit current
= peak value symmetrical breaking current
= 1.414 * 13.12 = 18.55 KA
4 – The making capacity of the breaker =1.8 * 18.55 =33.4 KA
5 – RMS value of the symmetrical breaking current = E / transient reactance
= 1.0 pu / 0.15 = 6.66
= 6.66 * 1.312 = 8.75 KA
6 - Asymmetrical breaking current = 1.4 * 8.75 = 12.25 KA
7 - The interrupting capacity of the circuit breaker = 1.73 * 6.6 *12.25 = 140 MVA
و هذا باختصر شديد مع مراعاة انه يجب الرجوع الى المواصفات الهندسية مثل
BS و IEC و ما شابه لاأختيار القيم الثابته و المعاملات حيث انها تختلف حسب
مستوى الجهد.
اختيار القاطع
اختيار القاطع الرئيسي
اختيار القاطع الكهربائي
اختيار القاطع المناسب
اختيار القاطع المناسب للمحرك
اختيار سعة القاطع
كيف يتم اختيار القاطع
كيف يتم اختيار القاطع الكهربائي
كيفية اختيار القاطع
كيفية اختيار القاطع الرئيسي
كيفية اختيار القاطع الكهربائي
كيفية اختيار القاطع الكهربى
كيفية اختيار القاطع المناسب
cb antenna selection
cb east course selection
cb jls group selection
cb jls group selection by user in registration
cb radio antenna selection
cb radio selection
cb rating selection
cb select
cb select beauty
cb select coffee
cb select homes
cb select professionals
cb select real estate
cb select storefront
cb select tulsa
cb selection
cb south course selection
wiggertaler selection cb
ليست هناك تعليقات: